K-IEPE and K-PT add-ons: specifications, pinouts and IEPE measurement

Updated

K-IEPE and K-PT are add-on modules that are not currently sold. This guide keeps their specifications, connectors and K-CAL setup in one place.

What the add-ons do

Both add-ons let a K-BOX or K-AN8 measure sensors its analogue inputs cannot read directly. Each connects to the host module's 25-way analogue connector with a 25-way cable and outputs signal voltages to its analogue inputs. You configure calibration and sampling rates in K-CAL.

  • K-IEPE (INF2213) powers up to four IEPE sensors, such as accelerometers, through BNC connectors. No other sensor supply is needed.
  • K-PT (INF2212) connects up to four PT100 or PT1000 resistance temperature detectors through two 9-way D-Sub connectors.

K-IEPE specifications

K-IEPE specifications
Item Specification
Measurement inputs 4, on BNC connectors
Internal resolution 18 bit
Internal sampling rate 6.25 kHz per channel
Data rate 1 kHz per channel on 4 channels, CAN at 1 Mbit/s
Input filter A digital filter in the ADC adjusts to the sampling rate automatically
High-pass filter 13.8 Hz
Bandwidth 21.8 Hz
Typical signal to noise ratio 102 dB
Linearity ADC ±0.75 LSB
Input impedance Above 10 kΩ
Input safety −0.7 V to +24 V permanent, with additional ESD protection
Broken sensor detection Yes
Sensor excitation Current source 5.1 mA ±2% at 24 V, 60 mA maximum in total for the 4 channels
Isolation 1000 V DC minimum on the CAN channel, between channel and power supply and between sensor excitation and power supply. CAN and power are galvanically connected.
Supply voltage 4.5 to 36 V DC
Power consumption Typically 2.6 W
Enclosure ABS, IP65, 128 × 46 × 105 mm, 450 g
Connectors 4 BNC signal inputs, two 9-way D-Sub CAN and power connectors carrying the same signals, one 25-way D-Sub to the host module
Operating temperature −40 °C to +85 °C

K-PT specifications

K-PT specifications
Item Specification
Measurement inputs 4
Sensors PT100 or PT1000, linearised with standard tables for the different alpha values
Measurement range −200 °C to +850 °C
Internal resolution 18 bit
Internal sampling rate 6.25 kHz per channel
Data rate 1, 2, 5, 10 or 20 Hz per channel
Hardware input filter Common-mode input filter and an output filter on the amplifier. Differential-mode corner 7.6 Hz, common-mode corner 159 Hz
Software input filter A digital filter in the ADC adjusts to the sampling rate. At 6.25 kHz sampling its frequency is 3 kHz
Measurement current 212 to 224 µA, depending on the sensor resistance
Gain error at 25 °C ±0.1% of the measured value
Offset and scaling error ±1 K
Gain drift ±10 ppm/K of the measured value
Zero drift ±5 mK/K
Broken sensor detection Yes
CAN interface CAN 2.0B up to 1 Mbit/s
Isolation 1000 V DC minimum on the CAN channel. CAN and power are galvanically connected.
Supply voltage 4.5 to 36 V DC
Power consumption Typically 1.9 W
Enclosure ABS, IP65, 115 × 46 × 105 mm, 450 g
Connectors Two 9-way D-Sub sensor connectors with two channels each, two 9-way D-Sub CAN and power connectors carrying the same signals, one 25-way D-Sub to the host module
Operating temperature −40 °C to +85 °C

K-IEPE connectors

Each IEPE sensor plugs into one of the four BNC connectors.

K-IEPE sensor input, BNC socket BNC · SOCKET K-IEPE sensor input, BNC socket Front view of one BNC socket on the module.CentreIEPE signalShellShield and signal returnSignal contactGround

The 25-way connector to the host module is a female D-Sub with nuts. Earlier documentation gives it the K-AN8 ADC table, with eight differential inputs and +24 V and +5 V outputs. That table does not fit a four-channel module.

K-PT connectors

The two sensor connectors are male 9-way D-Sub connectors with nuts. Each carries two 4-wire RTD channels. Ex is the excitation pair and Vs is the sense pair.

K-PT channel 0 and 1 connector, 9-way male D-Sub
Pin Function
1 Vs 1+
2 Vs 1−
3 Ex 1−
4 Ex 1+
5 Ground out
6 Vs 0+
7 Vs 0−
8 Ex 0−
9 Ex 0+
K-PT channel 2 and 3 connector, 9-way male D-Sub
Pin Function
1 Vs 3+
2 Vs 3−
3 Ex 3−
4 Ex 3+
5 Ground out
6 Vs 2+
7 Vs 2−
8 Ex 2−
9 Ex 2+
Wiring a PT100 or PT1000 element to K-PT channel 0 K-PT · 4-WIRE RTD Wiring a PT100 or PT1000 element to K-PT channel 0 K-PTchannel 0 and 1 connector9-way D-sub, male9Ex 0+6Vs 0+7Vs 0−8Ex 0−5Ground outExcitation current, 212 to 224 µASense: voltage at the elementPT100 or PT1000RTD elementSense pair, channel 0Terminal on the connectorConnectionEx carries the excitation current through the element; Vs senses the voltage at the element. Channel 1 uses pins 1 to 4 of the same connector, and channels 2 and 3 use the second connector in the same layout.

The 25-way connector to the host module is a female D-Sub with nuts. Earlier documentation repeats the K-AN8 ADC table for it, with eight differential inputs and +24 V and +5 V outputs. It warns not to apply voltages outside the range K-PT is configured for.

Screw terminals

9-way D-Sub screw terminals for RTD sensor wiring
Part number Description
INF4212.0 9-way D-Sub screw terminal, male, for PT sensor inputs and recommended for testing. 30 g, −20 °C to +80 °C
INF4212.1 9-way D-Sub screw terminal, female, for PT sensor inputs and recommended for testing. 30 g, −20 °C to +80 °C

Set up the add-on in K-CAL

On the Analog Channels tab, set Additional Board to the add-on you have connected. The tab then shows its settings. On a K-BOX, the thermocouple settings stay below them.

K-PT: the RTD settings

  • RTD(0-3): the CAN ID and rate at which the module sends the four RTD channels.
  • Sensor Type: Pt 100 or Pt 1000, set per channel.
The K-CAL Analog Channels tab with Additional Board set to RTD, RTD(0-3) CAN ID 0x183 at 1000 ms and sensor type Pt 100 on RTD 0 to RTD 3
The RTD settings with a K-PT connected.

K-IEPE: the IEPE settings

  • IEPE 0 to IEPE 3: a CAN ID and rate for each channel, the sensor Sensitivity in mV/g and the Offset in mV.
  • IEPE Transmit - Measure: Combined sends all the IEPE data in one CAN message with one CAN ID. Individual sends each IEPE channel with its own CAN ID.
The K-CAL Analog Channels tab with Additional Board set to IEPE, IEPE Transmit - Measure set to Individual and CAN ID, rate, sensitivity and offset for IEPE 0 to IEPE 3
The IEPE settings with a K-IEPE connected.

Measure IEPE sensors

Measure each sensor's offset at rest first, then enter it in K-CAL. The IEPE channels reach the host module on its odd analogue inputs: IEPE 0 on ADC 1, IEPE 1 on ADC 3, IEPE 2 on ADC 5 and IEPE 3 on ADC 7.

  1. Connect the add-on and the sensors. Connect the K-IEPE to the K-BOX and the IEPE sensors to the IEPE 0 to 3 inputs.
  2. Prepare the analogue channels. On the Analog Channels tab, set Additional Board to Not Connected and the software range of the odd channels to ±20 V.
  3. Measure the offsets. Keep the sensors at rest and open the Measurement tab. Note the values of ADC 1, ADC 3, ADC 5 and ADC 7 in mV.
  4. Enter the offsets and sensitivities. Back on the Analog Channels tab, set Additional Board to IEPE. Enter each noted value as the channel's Offset and the sensor's Sensitivity.
  5. Check the readings. Open the Measurement tab again.
  6. Export the DBC. Select Combined under IEPE Transmit - Measure, export the DBC file and import it into DIALOG.

For the pinouts of the host modules, see these guides:

Products in this guide

K-AN8

Analogue to CAN converter

View K-AN8 Ask an engineer

K-BOX

Multi-sensor data acquisition

View K-BOX Ask an engineer

Still stuck?

Our engineers answer support questions on every Influx Technology product.